GF 100 DV II Nordic QT
GF 200 DV II Lillehammer
Installation
and
Operation
Instructions
Jøtul GF 100 DV II
Nordic QT
Jøtul GF 200 DV II
Lillehammer
IF THE INFORMATION IN THESE INSTRUCTIONS
ARE NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-
SION MAY RESULT CAUSING PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE VICIN-
ITY OF THIS OR ANY OTHER APPLIANCE.
INSTALLATION:
INSTALLATION AND SERVICE MUST BE PER-
FORMED BY A QUALIFIED INSTALLER, SERVICE
AGENCY OR LICENSED GAS SUPPLIER.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL SWITCHES.
• DO NOT USE THE PHONE IN YOUR BUILDING.
IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A
NEIGHBOR’S PHONE.
• FOLLOW YOUR GAS SUPPLIER’S INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS SUPPLIER,
CALL THE FIRE DEPARTMENT.
WARNING:
THIS PRODUCT MUST BE INSTALLED BY A
LICENSED PLUMBER OR GAS-FITTER WHEN
INSTALLED IN THE COMMONWEALTH OF
MASSACHUSETTS.
A CARBON MONOXIDE (CO) DETECTOR SHALL
BE INSTALLED IN THE SAME ROOM AS THE
APPLIANCE.
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUC-
TIONS DANS CETTE NOTICE POUR REDUIRE AU
MINIMUM LE RISQUE D’INCENDIE OU POUR EVITER
TOUT DOMMAGE MATERIEL, TOUTE BLESSURE OU
MORTALIT’E.
NE PAS ENTREPOSER NI UTILISER D’ESSENCE NI
OU LIQUIDES INFLAMMABLES DANS LE VOISINAGE
DE CET APPAREIL OU DE TOUT AUTRE APPAREIL.
L’INSTALLATION LE SERVICE DOIVENT ETRE
EXECUTES PAR UN INSTALLATEUR QUALIFIE,
AGENCE DE SERVICE OU LE FOURNISSEUR DE
GAZ.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ.
• NE PAS TENTER D’ALLUMER L’APPAREIL
• NE TOUCHEZ A AUCUM NTERRUPTEUR.
• NE PAS VOUS SERVIR DES TELEPHONES SE
TROUVANT DANS LE BATIMENT OU VOUS VOUS
TROUVEZ.
• APPELEZ IMMEDIATEMENT VOTRE FOURNISSEUR
DE GAZ CHEZ UN VOISIN. SUIVEZ LES INSTRUC-
TIONS DU FOURNISSEUR.
• SI VOUS NE POUVEZ REJOINDRE LE
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE DES
INCENDIES.
Vue de la page 0
1 2 3 4 5 6 ... 31 32

Résumé du contenu

Page 1 - Instructions

1GF 100 DV II Nordic QTGF 200 DV II LillehammerInstallationandOperationInstructionsJøtul GF 100 DV IINordic QTJøtul GF 200 DV IILillehammerIF THE INFO

Page 2 - Welcome to Jøtul

10GF 100 DV II Nordic QTGF 200 DV II LillehammerVertical Vent TerminationThe Jøtul GF 100 DV II and Jøtul GF 200 DV II are ap-proved for vertical vent

Page 3 - Table of Contents

11GF 100 DV II Nordic QTGF 200 DV II LillehammerCo-linear Vent InstallationThis appliance may be vented through a masonry orClass A prefabricated chim

Page 4 - Specifications

12GF 100 DV II Nordic QTGF 200 DV II LillehammerFigure 12. Corner Installation, Horizontal Terminationdirectly off rear. Maximum Horizontal run is 2 f

Page 5

13GF 100 DV II Nordic QTGF 200 DV II LillehammerWall Shield InstallationThe decorative Wall Shield, included in the MiscellaneousHardware bag, is used

Page 6 - General Information

14GF 100 DV II Nordic QTGF 200 DV II LillehammerFigure 17. Vent Terminal Clearances - National Fuel Gas Code.Horizontal Termination ClearanceA = Clea

Page 7 - Safety Information

15GF 100 DV II Nordic QTGF 200 DV II LillehammerTools required:• 1/2” open ended wrench or deep-well socket, Torx T20or slotted screwdriver, 4 mm alle

Page 8 - Requirements

16GF 100 DV II Nordic QTGF 200 DV II LillehammerGas Conversion Procedure1. Turn off gas supply to stove.2. Remove the stove Top Plate (3).3. GF 100 DV

Page 9 - Venting Requirements

17GF 100 DV II Nordic QTGF 200 DV II LillehammerGas Supply ConnectionNOTE: If the optional Blower will be installed, use a 90°Elbow off the valve to c

Page 10 - Vertical Vent Termination

18GF 100 DV II Nordic QTGF 200 DV II LillehammerGas PressureCorrect gas pressure is essential for efficient and safeoperation. It is important that t

Page 11 - Venting Through a Fireplace

19GF 100 DV II Nordic QTGF 200 DV II LillehammerFlame Appearance -Air Shutter AdjustmentWARNING: AIR SHUTTER ADJUSTMENTS SHOULD ONLY BEPERFORMED BY A

Page 12 - Horizontal Vent Termination

2GF 100 DV II Nordic QTGF 200 DV II LillehammerWelcome to Jøtul...Congratulations on the purchase of your newJøtul gas heater.We at Jøtul are glad you

Page 13 - Wall Shield Installation

20GF 100 DV II Nordic QTGF 200 DV II LillehammerOptional Wall Thermostat orRemote ControlUse only a 750 millivolt DC two-wire circuit thermostatwith t

Page 14

21GF 100 DV II Nordic QTGF 200 DV II LillehammerSystem Check1. PURGING THE GAS LINE: When lighting the appli-ance for the first time, it will take a

Page 15 - Fuel Conversion

22GF 100 DV II Nordic QTGF 200 DV II LillehammerMaintenanceThis appliance and its venting system should be in-spected before use and at least annually

Page 16 - Gas Conversion Procedure

23GF 100 DV II Nordic QTGF 200 DV II LillehammerMODEL NAME: ________________________SERIAL NUMBER: ______________________DATE OF PURCHASE: ___________

Page 17 - Gas Supply Connection

24GF 100 DV II Nordic QTGF 200 DV II LillehammerMANUALAUTOOFFBLOWEROptional Blower # 155631Installation1. Unpack and check the con-tents of the blower

Page 18 - High Altitude Adjustment

25GF 100 DV II Nordic QTGF 200 DV II LillehammerBlower OperationThe variable-speed blower will enhance heat circulationaround the firebox and out into

Page 19 - Air Shutter Adjustment

26GF 100 DV II Nordic QTGF 200 DV II LillehammerGF 100 DV II / GF 200 DV IIIllustrated Parts Breakdown / Firebox Assembly Figure 39.A12344444456781011

Page 20 - Log Set Installation

27GF 100 DV II Nordic QTGF 200 DV II LillehammerPart Description Part Number1. Rear Shroud, Matte Black ...22055592Rear Shroud, Jøtul Iron

Page 21 - System Check

28GF 100 DV II Nordic QTGF 200 DV II LillehammerGF 200 DV II LillehammerIllustrated Parts Breakdown / Cast Iron and Associated HardwareGF 100 DV II No

Page 22 - Maintenance

29GF 100 DV II Nordic QTGF 200 DV II LillehammerCast Iron Parts ListGF 200 DV II Lillehammer4. Screw, M6 x 12 Truss Head Phillips, (4) ... 118045

Page 23 - GF 200 DV II Lillehammer

3GF 100 DV II Nordic QTGF 200 DV II LillehammerTable of ContentsSpecifications, GF 100 DV II ... 4Specifications, GF 200 DV II ...

Page 24 - Optional Blower # 155631

30GF 100 DV II Nordic QTGF 200 DV II LillehammerOptionalAntique Brick Panel Kit 155815Installation1. Remove the Top Plate. Simply lift it up off of t

Page 25 - Blower Operation

31GF 100 DV II Nordic QTGF 200 DV II Lillehammer3. Access the lower controls.4. Depress gas control knob slightly and turn clock-wise to

Page 26 - GF 100 DV II / GF 200 DV II

32GF 100 DV II Nordic QTGF 200 DV II LillehammerJøtul ASP.O. Box 1411N-1602 FredrikstadNorwayJøtul North America55 Hutcherson DriveGorham, Maine 0403

Page 27 - DEALER ONLY

4GF 100 DV II Nordic QTGF 200 DV II LillehammerJøtul GF 100 DV II Nordic QTSpecificationsInput RatesNatural Gas17,000 BTU/hr. maximum input 9,900 BT

Page 28

5GF 100 DV II Nordic QTGF 200 DV II LillehammerJøtul GF 200 DV II LillehammerSpecificationsGF 200 DV II Accessories• Fuel Conversion Kit - NG ...

Page 29 - Cast Iron Parts List

6GF 100 DV II Nordic QTGF 200 DV II LillehammerGeneral Information THIS HEATER MUST BE INSTALLED AND MAINTAINEDBY A QUALIFIED SERVICE AGENCY. The in

Page 30 - Antique Brick Panel Kit

7GF 100 DV II Nordic QTGF 200 DV II LillehammerLocationIn selecting a location for the stove, consider thefollowing points:1) Heat distribution2) Ve

Page 31 - LIGHTING INSTRUCTIONS

8GF 100 DV II Nordic QTGF 200 DV II LillehammerStove and Vent ClearanceRequirementsMinimum Clearances from the Stove to Combustibles:Measured from the

Page 32 - 138003 D

9GF 100 DV II Nordic QTGF 200 DV II LillehammerSEALANTVenting RequirementsBoth stoves may be installed with a vertical or horizontaltermination and mu